ולידציה – FRS Contents

ולידציה -FRS Contents

 This article was written by Iian Shaya, validation,automation and control expert

The FRS presents functional requirements for installing and operating a monitoring and control system, in response to and compliance with the user’s requirements

For example, the FRS may propose to fulfill the URS requirements using a system that includes a PC with control capabilities using HMI screens, PLC, and varied environmental conditions sensors and control devices. The FRS may also propose a color-code display for ongoing environmental conditions, including indications of alarm conditions. An SMS or e-mail notification may be sent to specified personnel in case of specified alarm conditions.

The FRS requirements are organized accordingly with the same order and numbering of sections as the URS for clear correspondence. These requirements are divided into 4 categories- as the user’s requirements

Installation Requirements

Operation Requirements

Regulation Requirements

HMI Requirements

Installation Requirements

These requirements cover all the issues regarding system installation to ensure its proper functionality and reliability. Examples of this type of requirements are

List and characteristics of specified hardware (HW) components capable of meeting the system functional requirements

Labeling and identification method for each HW component

List and characteristics of specified software (SW) programs installed on the system PC and the PLC, capable of performing the required operations

Definition of equipment to meet the storage capacity requirements

Definition of equipment and method for achieving the required connections to various types of sensors, communication units, temperature, humidity and pressure transmitters, illumination devices, etc

Definition of equipment and method for achieving the communication compatibility with equipment already installed at the user’s facility without extra sensors

Operation Requirements

These requirements cover all the operations that the system must be capable of performing. Examples of this type of requirements are

Environmental conditions (such as pressure, temperature and humidity) to be monitored and controlled

Type of systems to be monitored and controlled, such as Heating, Ventilation and Air Conditioning (HVAC) system, types of sensors, etc

Definition of computerized system capabilities and starting conditions

Definition of system capabilities to recover from failures

List of internal tests to be performed regularly, and alarm indications to be issued in case of failure

Definition of current and historical alarms to be provided regarding all parameters in any case of deviation from the limits specified in the system

Definition of system real-time screens display capabilities

Provision of the following data and HMI displays

Synoptic screens for displaying online values and status

Data logging and storage of historical trends, events and alarms

Tabular screens for displaying events and alarms

Graphical screens for displaying trends

Display of the following information for each alarm

Status -new/acknowledged alarm

Time at which the alarm was activated

Parameter/Tag/Name of the module that activated the alarm

Alarm Description

Alarm Priority

Display of alarms to warn the user, collect alarm history, and enable the user to view current and historical alarms. The system alarms shall include

Component malfunction/failure

Irregularity in parameter reading – such as disconnection of communication lines

Parameters values exceeding the high/low parameter limits

Deviations of system operation from predefined parameters/operations

Method for providing capability to configure the graphs parameters according to

Date and time

Measured parameters

Predefined number of displayed parameters

Definition of trend graphs with maximum and minimum allowed limits of the monitored parameters

Definition of logging interval defined by the user and configured by the supplier

Method for providing capability of authorized user’s personnel to define low and high limits and delay time for each

alarm parameter

On FRS regulatory & HMI Requirements you can find out in our next article

 This article was written by Iian Shaya, validation,automation and control expert

אילן שעיה מרצה Ilan Shaya